TYPICAL HANGER SPACING AND ROD DIAMETER FOR HORIZONTAL STEEL, PVC AND COPPER PIPING
Maximum Spacing
PVC *
Nominal
Pipe Size
Rod Diameter
Steel
Schedule 40
Schedule 80
Copper
3/8" - 1-1/4"
3/8"
7'
4'
4'
5'
1-1/2"
3/8"
9'
5'
5'
8'
2"
3/8"
10'
5'
6'
8'
2-1/2"
1/2"
11'
6'
6'
9'
3"
1/2"
12'
6'
7'
10'
3-1/2"
1/2"
13'
6'
7'
11'
4"
5/8"
14'
6'
7'
12'
5"
5/8"
16'
6'
7'
13'
6"
3/4"
17'
7'
9'
14'
8"
3/4"
19'
8'
9'
16'
10"
7/8"
22'
8'
10'
12"
7/8"
23'
9'
11'
14"
1"
25'
10'
11'
16"
1"
27'
10'
11'
Typical Hanger Types

Clevis Hanger
1/2 to 30 in. pipe

Pipe Clamp
1/2 to 24 in. pipe

Double Bolt Pipe Clamp
3/4 to 36 in. pipe
The data provided should be used only as a reference and not as a quarentee of performance. Installation must conform
with all local plumbing codes and regulations.
For more information about hanger spacing and rod diameters for steel, PVC and cooper piping
call the Advantage Sales Department at 317-887-0729.
Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142 Phone: 317-887-0729 Fax: 317-881-1277
Privacy Statement: we will not sell, rent or release any personal information you share with us to third party vendors.
Sitemap
Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability.
Products are assembled in the United States of America.
©2012 ADVANTAGE ENGINEERING, INC
Advantage Engineering Provides Industry Process Cooling Equipment For Optimizing Your Process