Process liquid chillers provide fluids between 20°F and 70°F (-7°C - 26°C) for cooling industrial applications. Central chillers are built onto an open frame for easy access to all serviceable parts.Process Liquid Chiller - 80-180 tons Air-Cooled Click Here

STANDARD FEATURES

RESERVOIR:
• Rotationally molded polyethylene
• One piece, seamless, cylindrical shape
• Insulated to prevent capacity loss
• Drain valve
• Overflow port
• Hot / cold section baffle
• Hinged tank cover
• Structural base
• Pump decking
• Automatic water level control
• Spare pump ports

REFRIGERANT CIRCUIT:
• Scroll compressor
• Compressor suction service valve
• Compressor discharge service valve
• Shell and tube evaporator
• Remote air-cooled condenser
  - with variable speed fans
  - with pressure staging
• Liquid receiver
• Oil separator
• Liquid line solenoid valve
• Refrigerant sight glass with
  moisture indicator
• Thermostatic expansion valve
• Hot Gas bypass capacity control

COOLANT CIRCUIT
• Large capacity process pump
    Suction service valve
   - Discharge service valve
• Evaporator pump
   - Suction service valve
   - Discharge service valve

LIMIT DEVICES (per zone)
• Refrigerant high pressure
• Refrigerant low pressure
• Evaporator flow
• Instrument circuit fuse

PRESSURE GAUGES (per zone)
• Refrigerant high Pressure
• Refrigerant low Pressure
• Coolant pressure

ELECTRICAL
• Fused transformer
• Nema rated electrical cabinet
• Power entry terminal block
• Fused compressor motor starter
  on dual and triple zone units

WARRANTY (US & Canada)
• 1 year parts and labor
   Warranty Statement For DownloadWarranty Statement

OPTIONS

FRAME
• Special Paint
• Stainless Steel Reservoir
• Epoxy coated mild steel reservoir

REFRIGERANT CIRCUIT
• Compressor CCPR valve
• Compressor hour meter

COOLANT CIRCUIT
• Larger process pumps
• Standby pump and manifold

CHILLER CONTROL INSTRUMENT
• Remote display kit
• PLC with touch screen display

WARRANTIES
• Extended compressor warranty

ELECTRICAL
• UL listed electrical panel
• Disconnect

CONTROL INSTRUMENT Multizone liquid chiller control instrument
Learn More about this instrument.

• Microprocessor based multizone controller
• Intelligent zone boards
• Compressors are staged individually
• Continuous To Process temperaturedisplay
• Continuous Setpoint temperaturedisplay
• Selectable from processtemperature display
• Large temperature display windows
• °F or °C temperature display
• Refrigerant circuit indicators for Probe, Low Flow, High Pressure, Low Pressure, Compressor,Freezestat, Capacity Control
• Water circuit indicators for Temperature Deviations, Low Pressure, Tank Level, Probe, Phase
• Selectable lead - lag mode
• Soft Key Operators
• SPI communications
• Audible and visual alarm

SPECIFICATIONS

Model: TI-80ASM

 
REFRIGERANT ZONES
QUANTITY: SO
COMPRESSOR
Quantity:
HP:
Type:
(1) Total Capacity: SO
(2) (3) PROCESS PUMP
HP:
GPM:
PSI: SO
EVAPORATOR PUMP
HP:
GPM: SO
CONNECTION SIZES
To Process:
From Process:
Make-Up:
Overflow: SO
(4) (5) FULL LOAD
AMPERAGE

230/3/60:
460/3/60:
575/3/60: SO
REFRIGERANT
Type: SO
RESERVOIR CAPACITY
Operating:
Holding: SO
DIMENSIONS
Height:
Width:
Depth: SO
(6) WEIGHTS
Shipping:
Operating:
SR
2
SN
 
2
40
Scroll
80 SS
 
15
240
70
SN
 
5
192
SN
 
4"
4"
1-1/2"
4"
SN
 
 

340.0
170.0
138.0
SN
 
R-407C
SN
 

1,200 gal
1,600 gal
SN
 
112"
136"
128"
SN
 
6,300 lbs
17,300 lbs
 
(7) REMOTE AIR-COOLED CONDENSER
SO
QUANTITY:
SO
(8) CONNECTION SIZES
Liquid:
Hot Gas: SO
(9) AIR FLOW
Fan Quantity: SO
(10) FULL LOAD
AMPERAGE

230/3/60:
460/3/60:
575/3/60: SO
DIMENSIONS
Height:
Width:
Depth: SO
(11) WEIGHTS
Shipping:
SN
1
SS
 
2-5/8"
1-5/8"
SN
 
6
SN
 
 

37.2
18.6
14.86
SN
 
49"
88"
187"
SN
 
2,340 lbs

Specification Notes:
1. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40. The minimum recommended operating temperature when no glycol is used is 48°F.
2. Consult pump curve for exact pump performance.
3. Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
4. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
5. Consult factory for 50HZ operation.
6. Unit weight crated for shipment. Air-cooled units shipped in two units. Basic field assembly required for Air-cooled units.
7. Specifications are shown for a single unit. Some models use multiple condenser units. Field charging required.
8. Field installation including piping connection and charging of remote air-cooled condenser by owner. Process connections may vary based on unique pump flow requirements of your process. Confirm you connection size requirement with your Advantage sales representative.
9. Vertical discharge from condenser.
10. Full load amperage shown for single condenser unit. Some models use multiple condenser units.
11. Unit weight crated for shipment.
12. See Warranty Statement #W-700 for details.

Advantage Products
6 Steps to Complete Central Chiller Information
Return to Step 1 : Select Condenser
Return to Step 2 : Select Reservoir
Return to Step 3 : Select System
Return to Step 4 : Select Capacity
Step 5 : View Unit Details
Step 6 : Get Pricing Now

Supporting Documents
Literature Literature
PDFPDF
2 Pages
Color
91 KB
Manual Manual
pdf logoPDF
56 pages
Color
520 KB
Knowledge Base
PDF HTML PDF & HTML
Documents covering the selection, service & operation of central liquid chillers.
American Flag Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142   Phone: 317-887-0729   Fax: 317-881-1277
Privacy Statement and Terms of Use.    Sitemap   Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability. Products are assembled in the United States of America.
©1998 - 2010 ADVANTAGE ENGINEERING, INC