OACS Series process water chillers are built onto an open frame for easy access to all serviceable parts.
STANDARD FEATURES
REFRIGERANT CIRCUIT:
• Available compressors:
- Scroll
- Screw
• Compressor suction service valve
• Compressor discharge service valve
• Brazed Plate or
Shell and tube evaporator
• Integral air-cooled condenser
- with variable speed fans
- with pressure staging
• Liquid receiver
• Liquid line solenoid valve
• Refrigerant sight glass with
moisture indicator
• Thermostatic expansion valve
• Capacity control
• Non-Ozone depleting refrigerant
COOLANT CIRCUIT
• Large capacity process pump
- Suction service valve
- Discharge service valve
• Evaporator pump (on two pump systems)
- Suction service valve
- Discharge service valve
• Reservoir
- Available as stainless steel, epoxy
coated mild steel, or polyethlene
- Full Insulation
- Drain Valve
- Hot/cold section baffle
(on systems with evaporator pump)
- Tank Lid
LIMIT DEVICES (per zone)
• Refrigerant high pressure
• Refrigerant low pressure
• Evaporator flow (Selected units only)
• Instrument circuit fuse
• Pump motor overload
• Low process pump pressure
(Selected units only)
PRESSURE GAUGES (per zone)
• Refrigerant high Pressure
• Refrigerant low Pressure
• Coolant pressure
WARRANTY (US & Canada)
• 1 year parts and labor
Warranty Statement
ELECTRICAL
• Outdoor rated electrical cabinet
• Fused transformer
• Fused pump motor starters
• Power entry terminal block
• Fused compressor motor starters
INSTRUMENT
Learn More about this instrument.
• Microprocessor based multizone
controller
• Intelligent zone boards
• Compressors are staged individually
• Continuous To Process temperature
display
• Continuous Setpoint temperature
display
• Selectable from process
temperature display
• Large temperature display windows
• °F or °C temperature display
• Refrigerant circuit indicators for
Probe, Low Flow, High Pressure,
Low Pressure, Compressor,
Freezestat, Capacity Control
• Water circuit indicators for
Temperature Deviations,
Low Pressure, Tank Level, Probe,
Phase
• Selectable lead - lag mode
• Soft Key Operators
• SPI communications
• Audible and visual alarm
OPTIONS
FRAME
• Special Paint
• Stainless Steel Reservoir
• Epoxy coated mild steel reservoir
REFRIGERANT CIRCUIT
• Compressor hour meter
COOLANT CIRCUIT
• Larger process pumps
• Standby pump and manifold
CHILLER CONTROL INSTRUMENT
• Remote display kit
• PLC with touch screen display
WARRANTIES
• Extended compressor warranty
ELECTRICAL
• UL listed electrical panel
• Main power disconnect
SPECIFICATIONS
Model: OACS-95-MZC-2P![]()
Specification Notes:
1. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by
the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40.
The minimum recommended operating temperature when no glycol is used is 48°F.
2. Consult pump curve for exact pump performance.
3. Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
4. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
5. PE = polyethylene; SS = stainless steel; MS = epoxy coated mild steel.
6. Approximate dimensions. Not for construction purposes.
7. See Warranty Statement #W-700 for details.